Micro Channel Heat Exchanger

Home / Product / Micro Channel Heat Exchanger / SC-1200 460*431.3mm Microchannel Tube Condenser Coil Heat Exchanger For Cooler
Home / Product / Micro Channel Heat Exchanger / SC-1200 460*431.3mm Microchannel Tube Condenser Coil Heat Exchanger For Cooler
SC-1200 460*431.3mm Microchannel Tube Condenser Coil Heat Exchanger For Cooler
  • SC-1200 460*431.3mm Microchannel Tube Condenser Coil Heat Exchanger For Cooler
  • SC-1200 460*431.3mm Microchannel Tube Condenser Coil Heat Exchanger For Cooler
Micro Channel Heat Exchanger

SC-1200 460*431.3mm Microchannel Tube Condenser Coil Heat Exchanger For Cooler

The microchannel tube condenser coil heat exchanger is a surprisingly green warmth dissipation tool utilized in coolers. Designed with microchannels, it gives a larger floor place for superior heat alternate. This equipment swiftly removes warmth from the refrigerant, maintaining a fab environment within the cooler. Its compact size permits for green heat dissipation in space-confined environments, resulting in stepped forward cooling efficiency. Suitable for numerous cooling applications, it proves to be a reliable answer for effective warmness transfer and temperature manage.
Contact Now
  • Description
Technical Data
Model Coil length Coil height Coil depth Fin pitch Fin height Manifold diameter
SC-1200 460[mm] 431.3[mm] 1.1[mm] 1.1[mm] 8.1[mm] 20[mm]
18.11[in] 16.98[in] 23[in] 23[FPI] 0.32[in] 0.79[in]

Model Tubes height Number of tubes Pass lnternal volume Inlet lD diameter Outlet lD diameter
SC-1200 1.3[mm] 43 14/12/10/7 ≈0.31[L] 7.94[mm] 6.35[mm]
0.05[in] ≈19[in³] 5/16[in] 1/4[in]

Mounting Bars
Aluminum MCHEs expand and contract when exposed to big temperature changes.Installation supports/bracketsmust allow the MCHE to move in two dimensions.


Performance Data

Air Velocity Performance [KW/Btu/hx1000]
[m/s] [ft/min] R410A R134a
=10K
=18°F
=15K
=27°F
=20K
=36°F
=25K
=45°F
=10K
=18°F
=15K
=27°F
=20K
=36°F
=25K
=45°F
1 197 1.78/6.08 2.82/9.62 3.83/13.07 4.84/16.52 1.72/5.87 2.65/9.04 3.65/12.46 4.61/15.73
1.5 295 2.54/8.67 3.94/13.4 5.35/18.26 6.78/23.14 2.35/8.02 3.74/12.7 5.08/17.34 6.41/21.88
2 394 3.18/10.8 4.94/16.8 6.71/22.90 8.51/29.04 2.9/9.90 4.65/15.8 6.31/21.54 7.95/27.13
2.5 492 3.75/12.8 5.83/19.9 7.93/27.06 10.07/34.3 3.49/11.9 5.46/18.6 7.42/25.32 9.33/31.84
3 591 4.28/14.6 6.65/22.7 9.06/30.92 11.5/39.25 3.95/13.4 6.19/21.1 8.4/28.67 9.33/31.84

Air Velocity Performance [KW/Btu/hx1000]
[m/s] [ft/min] R404A R407C
=10K
=18°F
=15K
=27°F
=20K
=36°F
=25K
=45°F
=10K
=18°F
=15K
=27°F
=20K
=36°F
=25K
=45°F
1 197 1.83/6.25 2.84/9.69 3.84/13.11 4.86/16.59 1.08/3.69 2.22/7.58 3.28/11.19 4.3/14.68
1.5 295 2.54/8.67 3.95/13.4 5.35/18.26 6.78/23.14 1.56/5.32 3.14/10.72 4.58/15.63 6.0/20.48
2 394 3.17/10.8 4.92/16.7 6.68/22.80 8.46/28.87 1.91/6.52 3.92/13.38 5.72/19.52 7.49/25.56
2.5 492 3.72/12.7 5.79/19.7 7.86/26.83 9.97/34.03 2.21/7.54 4.62/15.77 6.75/23.04 8.82/30.10
3 591 4.23/14.4 6.57/22.4 8.93/30.48 11.33/38.6 2.47/8.43 5.26/17.95 7.65/26.11 10.04/34.2

Air-side Pressure Drop Data
Air Velocity Pressure drop Flow rate
[m/s] [ft/min] [Pa]
[inch H2O] [m3/h]
[cfm]
1 197 9.23
0.04 653.08
384.2
1.5 295 14.52
0.06 979.62
576.5
2 394 22.11
0.09 1306.16
768.3
2.5 492 29.50
0.12 1632.70
960.4
3 591 35.40
0.14 1959.24
1152.5

  • Product Introducing:
Model: SC-1200
The Microchannel Tube Condenser Coil Heat Exchanger For Cooler, version SC-1200, is a cutting-edge product designed for maximum efficiency and sturdiness. With its compact dimensions and advanced microchannel era, it gives superior warmness transfer competencies, making it a super desire for a wide range of cooling programs.
Coil Dimensions:
Length: 460mm (18.11 inches)
Height: 431.3mm (16.98 inches)
Depth: 1.1mm (0.043 inches)
The coil's dimensions permit for a compact installation, saving precious area on your cooling machine.
Fin Details:
Pitch: 1.1mm (0.043 inches)
Height: 8.1mm (0.32 inches)
The fin pitch and top are optimized for optimum heat transfer, making sure green cooling performance.
Manifold Diameter:
Diameter: 20mm (0.79 inches)
The massive manifold diameter guarantees easy drift of refrigerant, minimizing stress drop and maximizing warmness transfer efficiency.
Features:
Microchannel Technology: The use of microchannels allows for a significantly large warmness transfer vicinity, improving universal warmness switch performance.
Compact Design: The compact dimensions of the condenser coil make it easy to integrate into various cooling structures.
Durability: Made from brilliant substances, the condenser coil is designed to resist the trials of every day use.
Efficient Heat Transfer: The optimized fin pitch and top, in conjunction with the microchannel design, make certain efficient warmth switch from the refrigerant to the encompassing air.
The Microchannel Tube Condenser Coil Heat Exchanger For Cooler, version SC-1200, is a dependable and green solution to your cooling needs. With its compact layout, superior era, and superior heat switch skills, it is certain to meet and exceed your expectancies.

Leave a Message

"If you have any comments or inquiries,please feel free to contact us"
// Zhejiang SunCo Heat Exchange System Co., Ltd.

Who Are We

We are a company specializing in R&D, production, and sales of heat exchangers, microchannel heat exchangers (MCHE), and fin tube heat exchangers. We are China Wholesale SC-1200 460*431.3mm Microchannel Tube Condenser Coil Heat Exchanger For Cooler Suppliers and SC-1200 460*431.3mm Microchannel Tube Condenser Coil Heat Exchanger For Cooler Factory. SunCo company is a group company with one production base in China Shaoxing with 72000 square meters, and one production base in Thailand with 25000 square meters, and an international company in Zhejiang Hangzhou and the US for sales, technical, and warehouse service. Company adhering to the "innovation, integrity, cooperation"business concepts, In way of comprehensively introducing ISO9001 & IATF16949 quality management system, with a good R&D team, reliable product quality, and highly efficient service to target the markets.
The company has robust design and development capability and specializes in designing many fields of air conditioning systems, and heat pipe heat exchange systems. It involved a variety of Industries, such as bus, tel-communications, commercial and industry refrigeration, frozen storage, rail transportation, wood drying, high-voltage substation, aerospace, etc. SunCo technology has won customers' deep trust.
Contact Us

Certificate

News

Micro Channel Heat Exchanger Industry knowledge

Are there any noise worries related to micro-channel heat exchangers with condenser coils?


There may be noise concerns associated with micro-channel heat exchangers with condenser coils. 
Micro-channel heat exchangers are an increasing number of being used in a whole lot of programs, along with aircon and refrigeration structures. They are designed to offer excessive warmness switch efficiency, compact size, and decreased weight. However, there are positive elements which could make contributions to noise era in these heat exchangers, specially in relation to the condenser coils.
One of the principle assets of noise in micro-channel heat exchangers with condenser coils is the go with the flow of refrigerant via the coils. The high-velocity glide of refrigerant can purpose turbulence and strain fluctuations, which in flip can result in vibration and noise era. This phenomenon is referred to as refrigerant-precipitated tone or whistling noise.
The geometry of the micro-channel heat exchanger also can have an effect on the noise degree. The design of the micro-channels, fins, and headers can impact the flow dynamics and pressure distribution inside the condenser coils, that could impact the noise generated. For instance, fallacious design or production tolerances can bring about non-uniform airflow, developing noise-producing regions and increasing normal noise tiers.
The material used inside the creation of the micro-channel heat exchanger can also effect the noise stage. Some substances generally tend to vibrate greater without problems than others, amplifying the noise generated by using refrigerant float. Additionally, the usage of light-weight materials, which is often desired in micro-channel heat exchanger designs, can cause elevated vibration and consequently greater noise.
The noise generated by micro-channel heat exchangers can be similarly amplified via the set up environment. Factors consisting of inadequate space across the heat exchanger, flawed mounting, or inadequate acoustic insulation can contribute to noise transmission and propagation. In certain cases, the noise can even be transmitted via the aircon or refrigeration ducts, impacting occupants within the surrounding location.
To deal with those noise worries, producers of micro-channel heat exchangers appoint several strategies. One technique is to optimize the layout of the heat exchanger to reduce turbulence and pressure fluctuations within the refrigerant float. This can involve modifications to the geometry of the micro-channels, fins, and headers to enhance go with the flow dynamics and reduce noise-producing areas. Additionally, improving manufacturing techniques and tightening tolerances can help lessen non-uniform airflow and associated noise.
Another technique is to hire noise reduction technology, inclusive of the usage of sound-absorbing materials or adding acoustic insulation across the heat exchanger. These strategies can assist attenuate the noise generated via the micro-channel heat exchanger and save you its transmission to the encompassing environment.
Furthermore, producers can behavior large checking out and assessment of the micro-channel heat exchangers to pick out and address any ability noise problems. This can encompass laboratory measurements of sound strength levels, sound exceptional exams, and computational fluid dynamics simulations to optimize the design parameters.